As a professional copper busbar manufacturer, Wuxi Xinda Ke has introduced you to a lot of knowledge about copper busbars in previous articles. Today, let's learn about the installation of copper busbars. When installing copper busbars, you must wear gloves to prevent stains. Do you know what other requirements there are?

1. Gloves must be worn during copper busbar assembly to prevent fingerprints and stains from leaving on the surface.

2. Fasteners used for copper busbar connections should use galvanized bolts/screws, nuts, and washers that meet national standards.

3. The length of combined screws should be such that after tightening, 2–5mm of the thread protrudes beyond the nut. The length of hexagonal head bolts/round head square neck bolts should be such that after tightening, 5–8mm of the thread protrudes beyond the nut, and should not be too long or too short.

4. The general direction for the bolts to pass through is usually from bottom to top, from back to front, and from left to right, striving for uniformity. When the copper busbar is placed horizontally, the bolts and nuts for connection should be tightened from bottom to top; in other cases, the nuts should be installed on the side that is convenient for maintenance.

5. Both sides of the bolt connecting the T2 copper busbar must have flat washers, and the nut side should have a spring washer or lock washer. There should be a clear spacing of more than 3mm between the washers of adjacent bolts to prevent the formation of magnetic circuit heating.

6. Generally, it is not advisable to overlap three copper busbars at one place, specific requirements depend on the design and process documents.

7. The contact surface of the copper busbar should be connected tightly. The connecting bolts should be tightened with a torque wrench for confirmation and marked. The connecting combination screws should be tightened with a torque driver for confirmation and marked. The tightening torque value should comply with the provisions of the "Threaded Fastening Process Specification".

Copper bus manufacturer

8. Busbar Price: Busbar installation should be flat and aesthetically pleasing. During busbar installation: Horizontal sections: The height error between two support points should not exceed 3mm, and the total length error should not exceed 10mm. Vertical sections: The vertical error between two support points should not exceed 2mm, and the total length error should not exceed 5mm. Spacing: The spacing of parallel sections should be uniform and consistent, with an error not exceeding 5mm.

9. When two or more rectangular copper busbars are connected in parallel, ensure that the gap between the parallel copper busbars is not less than their thickness to allow for heat dissipation.

If you want copper busbars, then it is Yixing Xindake New Energy Technology Co., Ltd. Our company specializes in copper foil flexible connectors, copper busbar manufacturing, and stamping parts processing prices. Thank you for your browsing and support!


Previous: Copper busbars differ not only in hardness but also in processing methods.
Next: Has the processing technology of stamping parts improved with technological changes?

Phone:

0510-87183933

Leave a Message

Name:   
Phone:
Email:
Message:      
Submit